摘要(英) |
With the development of smart grid, the effective detection and identification of voltage variation events become important tasks for the protection of microgrid and power system monitoring integrated different distributed energy systems. When power quality events happened, these events usually caused large losses in commercial and industrial consumers are the main events in power systems due to the sensitivity of equipment to these voltage variations. In addition, in recent years, the widely applications of power electronics technique, and the amount of non-linear loads increased on power system, harmonic problem become more important.
There are a lot of analysis methods in tradition. For example, Zero-crossing is used to analyze the fundamental frequency, Fast Fourier Transform is used to analyze the harmonics, etc. Take FFT for example, although the simple calculation procedure and the high computational efficiency are the advantages of FFT, there exist some limitations needed to meet. If it didn′t, the aliasing, the leakage effect, and the picket-fence effect may occur. Though It could increase the sampling points to improve the frequency resolution, it will deteriorate the computational efficiency.
The keypoint of this thesis is high resolution, great efficacy and including analysis of multiple power events. According to aforementioned considerations, Prony method is used and plays an important role in analysis of power events. A SCADA of power quality events is developed. With advantages of multiple power events analysis, less limitation, better computational efficiency, power quality events can be detected correctly and activate the protection or compensation devices avoiding damage of power system.
|
參考文獻 |
[1] J. W. He, Y. W. Li, and F. Blaabjerg, “Flexible Microgrid Power Quality Enhancement Using Adaptive Hybrid Voltage and Current Controller,” IEEE Trans. Ind. Electron., Vol. 61, No. 6, pp. 2784-2794, June 2014.
[2] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero, “Autonomous Voltage Unbalance Compensation in an Islanded Droop-Controlled Microgrid,” IEEE Trans. Ind. Electron., Vol. 60, No. 4, pp. 1390-1402, April 2013.
[3] T. L. Lee, S. H. Hu, and Y. H. Chan, “D-STATCOM With Positive-Sequence Admittance and Negative-Sequence Conductance to Mitigate Voltage Fluctuations in High-Level Penetration of Distributed-Generation Systems,” IEEE Trans. Ind. Electron., Vol. 60, No. 4, pp. 1417-1428, April 2013.
[4] 江榮城,「電力品質」,全華圖書,2007出版。
[5] IEEE Std. 1159-2009, Recommended practice for monitoring electric power quality, New York, 2009.
[6] 翁建昆,使用DSP於風力電力發電系統電壓與頻率之檢測,中原大學電機工程學系碩士學位論文,民國94年7月。
[7] C.Y.Chen, “High-Resolution SVD Method for Waveform Processing by Using Down-Sampling Technique,” Institute of Electrical Engineering College of Engineering National Chung Cheng University, July 2006 Chiayi, Taiwan, Republic of China.
[8] P. K. Dash, D. P. Swain, A. C. Liew and S. Rahman, “An adaptive linear combiner for on-line tracking of power system harmonics, ”IEEE Trans. on Power Systems, Vol. 11, No. 4, Nov. 1996, pp.1730-1735.
[9] IEEE Draft Recommended Practice for Adoption of IEC 61000-4-15:2010, Electromagnetic compatibility. (EMC--Testing and measurement technique--FlickermeterFunctional and design specifications)
[10] 中華技術學院,電力品質不良因素與管制標準研究。
[11] Alexander Novitskiy, Holger Schau, “ Analysis of a Ratio between 〖∆V〗_10 and P_stFlicker Criteria”, UPEC 2011, 46th International Universities′ Power Engineering Conference ∙,5-8th September 2011 Soest Germany.
[12] 日本電氣學會技術報告(II)部第72號,製鋼用電弧爐電力供給問題最新動向,電氣加熱技術學會,昭和53年(1978)。
[13] 臺灣電力股份有限公司電壓閃爍管制要點,民國95年8月16日。
[14] IEEE P1564/D13 ,Draft Guide for Voltage Sag Indices ,August 2010.
[15] G.W. Chang, C.I. Chen, Y.J. Liu and M.C. Wu, Measuring power system harmonics and interharmonics by an improved fast Fourier transform-based algorithm.
[16] Cheng-I Chen, Member, IEEE, A Phasor Estimator for Synchronization Between Power Grid and Distributed Generation System.
|