    题名: 微電網之孤島與併網模式切換技術;Switching Technology of Islanding and Grid-Connected Modes for Microgrid
    作者: 呂賀為;Lyu, He-Wei
    贡献者: 電機工程學系
    关键词: 微電網;孤島模式;併網模式;同步參考軸鎖相迴路;Microgrid;Islanding Mode;Grid-Connected Mode;SRF-PLL
    日期: 2018-08-24
    上传时间: 2018-08-31 14:56:46 (UTC+8)
    出版者: 國立中央大學
    摘要: 本文旨在實現一演算法,使微電網能順利地在孤島與併網模式間進行切換且能穩定運作,為了能順利將微電網併上市電,首先需測量微電網端之三相電壓值,透過鎖相迴路計算其相位角,並符合併網相關規範。相位檢測採用同步參考軸鎖相迴路(Synchronous Reference Frame,SRF-PLL),其優勢是架構最為簡單,當微處理器在運算時可簡化運算之複雜度,且容易實現。
    文中利用Matlab/Simulink模擬一微電網之架構,並用Dev-C++模擬演算法並驗證其可行性,最後將演算法寫入Renesas RX62T微處理器做運算。在硬體部分以三相四線半橋式變流器模擬一微電網,藉由演算法可將變流器在孤島與併網模式下切換,利用電壓、電流感測電路將三相輸出電壓、電流拉回微處理器做運算,即達到閉迴路控制之目的。

    關鍵字:微電網、孤島模式、併網模式、同步參考軸鎖相迴路
    ;Abstract
    The purpose of this thesis is to implement an algorithm that enables the microgrid to switch between islanding and grid-connected operation modes smoothly and to operate stably. To be able to successfully grid-connected with utility grid, it is necessary to measure the three-phase voltage of the microgrid first. Calculate the phase angle through the phase-locked loop and meet the related grid codes or regulations. The phase detection adopts Synchronous Reference Frame (SRF-PLL). The advantage is that the topology is the simplest. When the microprocessor is in operation, it can simplify the computational complexity and it is easy to implement.

    This thesis uses Matlab/Simulink to simulate the architecture of a microgrid and uses Dev-C++ simulation algorithm to verify its feasibility. Finally, the algorithm is written into the Renesas RX62T microprocessor for operation. In the hardware implementation, a microgrid is simulated by a three-phase four wire, half-bridge inverter. The inverter can be switched between island and grid mode by using the proposed algorithm. The voltage and current sensing circuit are used to output the three-phase voltage. The current is recall or feedback to the microprocessor for closed- loop operation control.

    Keywords: Microgrid, Islanding Mode, Grid-Connected Mode, SRF-PLL